DS92 (device messages)
Byte Meaning Note 3RK3 Basic 3RK3 Advanced
3RK3 ASIsafe
Error cat‐
egory
DP error
number
Error cat‐
egory
DP error
number
26
0
Memory module not plug‐
ged in
A memory module has not been
plugged in.
SF F24, F26 SF, KF F24, F26
26
1
Memory module defective The memory module is defective. SF F24, F27 SF, KF F24, F27
26
2
Reserved = 0
26
3
Memory module program‐
ming successful
The con󹪝guration data was suc‐
cessfully saved in the memory
module.
26
4
Programming error The con󹪝guration data could not
be saved in the memory module.
SF F24, F27 SF, KF F24, F27
26
5
User memory too small The con󹪝guration data does not 󹪝t
into the con󹪝guration memory or
onto the memory module.
SF F24, F7 SF, KF F24, F7
26
6
Reserved = 0
26
7
Memory module deleted The con󹪝guring data has been de‐
leted.
27
0
Reset performed Reset has been performed.
27
1
Reset was not possible Reset was not possible
27
2
... 29
3
Reserved = 0
29
4
Self-test active The system is executing a self-test.
29
5
Self-test OK The self-test was successful.
29
6
Self-test error (device error) A self-test error occurred. GF F24, F9 GF, SF F24, F9
29
7
... 33 Reserved = 0
34 ... 35 Incorrect element number Element number of the 󹪝rst ele‐
ment found in the con󹪝guration
whose parameters were not accep‐
ted by the device:
[0]: no incorrect element exists
[1 ... 32767]: (unsigned int) el‐
ement no.
DP 󹪝eldbus interface:
36
0
CPU/master STOP The DP master is in the STOP state.
36
1
DP bus error PROFIBUS error, connection inter‐
rupted
BF F19 BF F19
36
2
DP parameterization error Erroneous or incorrect parameter‐
ization frame
BF
36
3
DP con󹪝guration error Erroneous or incorrect con󹪝gura‐
tion frame
BF
36
4
DP process data exchange
stopped
Process data exchange with DP
master stopped.
36
5
DP communication OK DP communication is OK
36
6
... 37
7
Reserved = 0
AS-i 󹪝eldbus interface
Diagnostics / service
7.11 Description of the diagnostic data sets