DS92 (device messages)
Byte Meaning Note 3RK3 Basic 3RK3 Advanced
3RK3 ASIsafe
Error cat‐
egory
DP error
number
Error cat‐
egory
DP error
number
38
0
AS-i bus error AS-i data exchange interrupted,
substitute values in process image
‑ BF F19
38
1
AS-i parameterization error Simulated slave is not incorpora‐
ted in the communication of the
AS‑i master
‑ BF F19
38
2
AS‑i conguration error In addition, the AS-i address of the
aected AS-i slave with the lowest
address is entered in byte 39. For
example, set for TARGET ≠ ACTUAL
subslot expanded conguration
‑ BF ‑
38
3
... 38
4
Reserved = 0
38
5
AS-i communication OK AS-i communication is OK ‑ ✓
38
6
... 38
7
Reserved = 0
39 Incorrect AS‑i address AS-i address of AS-i slave identied
as faulty by the device
• [0x00]: no AS-i address exists
• Bit 0 ... 4: address
1 ... 31[1 ... 31]
• Bit 5: A address [0] B address
[1]
• Bit 6: Standard slave [0] A/B
slave [1]
• Bit 7: reserved [0]
‑ BF ‑
40 ... 43
44
0
AS-i slave function active At least one AS-i slave is being si‐
mulated
‑ ✓
44
1
... 44
7
Reserved = 0
45 Reserved = 0
46
0
AS-i monitor function active At least one AS-i slave is being
monitored
‑ ✓
46
1
... 47 Reserved = 0
ASIsafe:
48
0
ASIsafe 8x4-bit code se‐
quence monitor active
At least one safety-related AS-i
slave is being monitored
‑ ✓
48
1
ASIsafe 7x4-bit code se‐
quence generator active
At least one safety-related AS-i out‐
put is being monitored
‑ ✓
48
2
ASIsafe 8x4-bit code se‐
quence generator active
At least one safety-related AS-i sen‐
sor is being simulated
‑ ✓
48
3
ASIsafe 7x4-bit code se‐
quence monitor active
At least one safety-related AS-i out‐
put is being simulated
‑ ✓
48
4
... 48
7
Reserved = 0
Diagnostics / service
7.11 Description of the diagnostic data sets
SIRIUS 3RK3 Modular Safety System