7.10 Analog Output Trim
FUE1010 IP65 NEMA 4X
124 Operating Instructions, 12/2014, A5E03086491-AC
To calculate a current output:
1. Set up an ammeter to read amps, then connect it to the supply and return terminals of the
current output under test.
2. Move the highlight to the port to be tested, press <Right Arrow> and then press <Down
Arrow> to move the cursor to [Trim @ 4mA].
3. Press <ENTER>. This triggers a 4.00 mA pop-up window. The ammeter will now be
reading 4.00 mA.
4. If the ammeter reading does not match, use the numeric keys to type in the ammeter
reading.
5. Pres<ENTER> to register setting. This adjusts the flow meter’s DAC (digital-to-analog
converter) so that a 4mA output corresponds with 4mA on the ammeter.
6. Re-check the ammeter to make sure that it is now reading 4mA.
Voltage Output Trim (Vo1 & Vo2)
Note
Can be trimmed to within .0025 V of nominal.