Communication
11.1 Integration in SIMATIC S7-1200
SIWAREX WP231
152 Manual, 07/2014, A5E31238908A-02
Error codes of function block
Table 11- 3 Statuses/errors when working with the function block
bo_ApplIDError Address module does not match the function block
bo_ApplIDDRError Data record does not match the inserted module
bo_SFBError Runtime error during transmission of data record
bo_RdPerError Reading of I/O data failed
bo_LifeBitError SIWAREX no longer responds
bo_StartUpError Command was sent although StartUp is still TRUE
bo_WrongFW Data record version does not match the firmware
bo_InvalidCMD An invalid command code was sent
bo_DataOperationError Synchronous data operation error has occurred
bo_StartUp Startup synchronization of module running
If execution of the function block is faulty, the variables shown do not correspond to the
actual status in the module.