Technical data
13.2 Electrical, EMC and climatic requirements
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
169
13.2
Electrical, EMC and climatic requirements
Electrical protection and safety requirements
Table 13- 12 Requirements: Electrical protection and safety requirements
Met requirement
Standards
Comments
Safety regulations IEC 61010-1
IEC 61131-2; UL 508
CSA C22.2 No.142
Protection class IEC 61140 Module is operated with protective extra-low
voltage.
The protective conductor connection serves
only a functional earth to dissipate interfer-
ence currents
IP degree of protection IP 20 to IEC 60529
Protection against contact with
standard probe
Protection against solid bodies with
diameters in excess of 12.5mm
No special protection against water
Air gaps and creepage distanc-
es
IEC 60664
IEC 61131-2
IEC 61010-1
UL 508
CSA C22.2 No. 145
EN 50156-1
Overvoltage category II
Pollution degree 2
PCB material IIIa
Conductor path distance 0.5 mm
Isolation stability IEC 61131-2
CSA C22.2, No. 142
UL508
Ethernet Port:
1 500 V AC (shield and signals)
Additional electrical circuits:
Test voltage:
500 V AC or 707 V DC
Test duration: ≥ 1 minute
Short circuit current: ≥ 5 mA