Scale parameters and functions
8.6 DR 5 zeroing memory
SIWAREX WP231
82 Manual, 07/2014, A5E31238908A-02
Data record DR 5 displays the current values in the tare memory and the zeroing memory.
In legal trade operation, the data record is not write-protected.
● Check all parameters
● Transfer the data record to the scales
Table 8- 3 Assignment of data record 5
Data record
number
Contains no. of data
record
USHORT 2 r 5 - - 1214
Length Data record length in-
formation
USHORT 2 r 40 - - 1215
Application Information about which
application the DR be-
longs to
USHORT 2 r 101 - - 1216
Version identi-
fier
Information about the
current data record
version
USHORT 2 r 1 1 65635 1217
Effective tare
weight - from
specification 1,
2 or 3
(Page 83)
Current tare weight (tare
setting)
FLOAT 4 rwP 0 0 Depends
on specifi-
cation in
DR 3
1218
Effective tare
weight (semi-
automatic)
(Page 83)
Current tare weight
(semi-automatic)
FLOAT 4 rwP 0 0 Depends
on specifi-
cation in
DR 3
1220
Zero by power-
on (value when
switching on)
Current zero by power-
on weight (affected by
switch-on)
FLOAT 4 rwP 0 Depends
on specifi-
cation in
Depends
on specifi-
cation in
1222
Zero weight
(semi-
automatic)
(Page 83)
Current zero weight
(semi-automatic)
FLOAT 4 rwP 0 Depends
on specifi-
cation in
DR 3
Depends
on specifi-
cation in
DR 3
1224
Current zero
tracking weight
(Page 83)
Current zero weight
(zero adjustment)
FLOAT 4 rwP 0 Depends
on specifi-
cation in
DR 3
Depends
on specifi-
cation in
DR 3
1226
Dead load
(Page 83)
Dead load calculated
during automatic calibra-
tion
FLOAT 4 r 0 Depends
on specifi-
cation in
DR 3
Depends
on specifi-
cation in
DR 3
1228
Reserve 1 Reserve SHORT 2 rw 0 - - 1230
Reserve 2 Reserve USHORT 2 rw 0 - - 1231
Reserve 3 Reserve FLOAT 4 rw 0 - - 1232