EasyManua.ls Logo

Siemens SIWAREX WP231 - Table 13- 13 Requirements: Interference Emission in Industrial Area in Accordance with en 61000-6-4

Siemens SIWAREX WP231
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
13.2 Electrical, EMC and climatic requirements
SIWAREX WP231
170 Manual, 07/2014, A5E31238908A-02
Electromagnetic compatibility
Table 13- 13 Requirements: Interference emission in industrial area in accordance with EN 61000-6-4
Comments
Standard
Limits
Emission of radio interferences
(electromagnetic fields)
Class A industrial environment:
EN 61000-6-4
IEC/CISPR 16-2-3: 2008
30 ... 230 MHz,
40 dB (μV/m) Q
230 ... 1 000 MHz,
47 dB (μV/m) Q
Emission on power supply cables
24 V
Class A: Industrial environment:
EN 61000-6-4
IEC/CISPR 16-2-1: 2010;
EN 55016-2-1: 2009
Class A: Industrial environment
0.15 ... 0.5 MHz, 79 dB (μV)
Q
0.15 ... 0.5 MHz, 66 dB (μV)
M
0,5 ... 30 MHz, 73 dB (μV) Q
0,5 ... 30 MHz, 60 dB (μV) M
Emission conducted Ethernet EN 61000-6-4 0.15 ... 0.5 MHz:
53 dB (μA) to 43 dB (μA) Q
40 dB (μA) to 30 dB (μA) M
0.5 ... 30 MHz:
43 dB (μA) to 30 dB (μA) M