27
Rule 4: Special EMC measures
● All inductors that are to be controlled should be connected with suppressors.
● For cabinet or enclosure lighting in the immediate range of your controller, use
incandescent lamps or interference suppressed fluorescent lamps.
Rule 5: Homogeneous reference potential
● Create a homogeneous reference potential and ground all electrical equipment.
● Use sufficiently dimensioned equipotential bonding conductors if potential differences
exist or are expected between your system components. Equipotential bonding is
absolutely mandatory for applications in hazardous areas.