Instruction Manual
for
AS380 Series Elevator Integrated Drive Controller
160
any point within that range is set as constant open, the corresponding bit should be set as
zero. When any point within that range is set as constant close, the corresponding bit
should be set as one. The parameter in operator is set point by point(one bit after
another)during the actual operation. Therefore there is no need to calculate the value.
F27—— Car wall-mounted control board input selection. Constant open/close setting for switch
input point GX0-GX15 of car board. It is 16 bit data. The bottom bit for GX0, The
ceiling bit for GX15. When any point within that range is set as constant open, the
corresponding bit should be set as zero. When any point within that range is set as
constant close, the corresponding bit should be set as one. The parameter in operator is
set point by point(one bit after another)during the actual operation. Therefore there is
no need to calculate the value.
F28—— Car ceiling-mounted control board selection. Constant open/close setting for switch
input point HX0-HX15 of car ceiling. It is 16 bit data. The bottom bit for HX0, The
ceiling bit for HX15. When any point within that range is set as constant open, the
corresponding bit should be set as zero. When any point within that range is set as
constant close, the corresponding bit should be set as one. The parameter in operator is
set point by point(one bit after another)during the actual operation. Therefore there is
no need to calculate the value.
Note: supplementary explanation for input type setup.
HX6—— The overload switch must be constant close switch. If the constant open switch is
used, it will not work if the overload switch broken down or the overload circuit
disconnected. The failure to detect an overload situation would most likely to put the
elevator in service in danger.
So are the limit switches and terminal deceleration switches and etc. constant close
contact recommended. Otherwise potential safety hazard may occur to the elevator.
HX4—— NO-Load switch( input at this point means that the car is no-load. The action point
of the switch is the load of less than 100 KG
If this switch is not in use, the HX4 must be set as constant open.
Otherwise, the system will permanently identify the car as no-load. The following
consequence will occur. When the system in the elevator detect more than 5 call
registrations (according to the parameter setting of F120), the system mistakenly
identify the car as no-load. The system in the elevator indentifies so many call
registrations as the result of children making trouble. The system will activate
anti-nuisance function and cancel all the existing call registration in order to reduce
waste.
HX7—— door-opening limit switch for rear door, HX8 door-closing limit switch for
Rear door and HX10 safety edge for rear door
If there is no rear door for the elevator, HX7 set as constant open, HX8 as constant close,
HX10 as constant open. The setting of the elevator with rear door should be in
conformity with the actual condition.
F29—— Service floor 1, F29 value set whether the actual floor sequence from 1 to 16 is allowed
to park or not. It is 16 bit data. The bottom bit for the lowest floor, The ceiling bit for
16
th
floor. When any point within that range is set as one, the corresponding floor
should be set as service floor for parking. Vice versa, when any point within that range