Innagator | Technical Pack115
Concerningthedetailednextgures:
1. Tickthisboxtonotexportpowerbacktothegrid(theCTcoilwilldetectpowerowingbacktothegrid
and will reduce the power of the inverter only to supply the local load).
2. Tick this box if you wish to export your solar power back to the grid.
3. Tick this box if you only want to supply power to the load side of the inverter.
4. ‘ZeroExportPower’istheamountofpowerowingfromthegridtotheinverter.Setthisvalueto’20-
100W’ to instruct the inverter to always take the prescribed amount of power from the grid to minimise
the tripping of sensitive pre-paid electricity meters if ‘Reverse Power Detection’ occurs.
5. This controls the maximum overall power, both to the ‘Load’ and ‘Grid’ ports combined. It is set to Low if
an ‘over-current’ fault occurs.
6. Tick this box if you wish to set the solar panels to give power to the ‘Load’. If you untick this box, the solar
will send power to charge the batteries.