Fault76:48VKeySwitchUndervolt—CRM1
Important:Forthisfault,theterm“keyswitch”referstothe48Vdclogicpowercircuit,nottothe
ignitionswitch.
Note:Whenanyindividualcuttingreelmotorisshutoffduetoafault,theTEC-5002shutsofftheother4
cuttingreelmotors.
Note:Ifmultiplemachinefaultsarereportedwithinafewseconds,troubleshootingshouldbeginwiththe
rstcuttingreelmotortoreportafault.
InfoCenterDisplay:
_____ FAULT#76 _____
48V LOV 1
FaultDescription
Akeyswitchundervoltagefaultisreportedwhenthecuttingreelmotormeasuresalogicvoltagelowerthan
32Vdc.
CircuitDescription
Eachcuttingunithasanelectriccuttingreelmotorthatcontainsaninternalcontroller.Theinternalcontroller
measures48Vdclogicpower,andtheelectriccuttingreelmotormeasures48Vdcbuspower.
Ifonly1cuttingreelmotorisreportingakeyswitchundervoltfault,theproblemismorelikelytobewiththe48
Vdclogicpowerconnectiontothatcuttingreelmotor.
Ifmorethan1cuttingreelmotorisreportingakeyswitchundervoltfault,theproblemismorelikelytobe
withthe48Vdcbusvoltage.
ConditionsforSettingtheFault
Cuttingreelmotor1detectsthatthe48Vdclogicvoltageisbelowtheminimumof32Vdcandreportsthisfault.
RecommendedServiceActions
Step1:Verifythatthefaultrepeats.
1.ClearthesystemfaultsfromtheInfoCenter.RefertoClearingFaultsfromtheInfoCenter(page21).
2.Operatethemachine.
Pass
Thefaultdidnotrepeat.GotoReturningtheMachinetoService(page22)andfollowthestepslisted.
Note:Ifthefaultdoesnotrepeat,anisolatedeventhasoccurred.
Fail
Thefaultrepeated.GotoStep2.
Step2:Determinethetroubleshootingstrategy.
Ifonly1cuttingreelmotorisreportingakeyswitchundervoltfault,theproblemismorelikelytobewiththe
48Vdclogicpowerconnectiontothatcuttingreelmotor.GotoStep3.