18 Technical data
18.1 Technical data
Thermostat T-163, T-165, T-166, and T-168
IP IP20, class III (IP: degree of inaccessibility to active parts of the product
and degree of water)
Max. ambient RH (relative humidity) 85% at 20 °C
CE marking
ERP IV
Low voltage tests EN 60730-1* and EN 60730-2-9***
EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3
ERM (electromagnetic compatibility and radio spectrum matters) tests EN 300 220-3
Power supply Two 1.5 V AAA alkaline batteries
Voltage 2.2 V to 3.6 V
Rated impulse voltage 0.33 kV, OVC I
Pollution degree 2
Software class A
Operating temperature 0 °C to +45 °C
Storage temperature -10 °C to +65 °C
Radio frequency 868.3 MHz
Radio frequency, EAC markets only 869 MHz
Transmitter duty cycle <1%
Connection terminals 0.5 mm² to 2.5 mm²
Thermostat T-161 and T-169
IP IP20, class III (IP: degree of inaccessibility to active parts of the product
and degree of water)
Max. ambient RH (relative humidity) 85% at 20 °C
CE marking
ERP IV
Low voltage tests EN 60730-1* and EN 60730-2-9***
EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3
ERM (electromagnetic compatibility and radio spectrum matters) tests EN 300 220-3
Power supply 1 x CR2032 3V
Voltage 2.4 V to 3.6 V
Rated impulse voltage 0.33 kV, OVC I
Pollution degree 2
Software class A
Operating temperature 0 °C to +45 °C
Storage temperature -10 °C to +65 °C
Radio frequency 868.3 MHz
Radio frequency, EAC markets only 869 MHz
Transmitter duty cycle <1%
Connection terminals 0.25 mm² to 0.75 mm² solid, or 0.34 mm² to 0.5 mm² flexible with ferrules
Thermostatic head T-162
IP IP20, class III (IP: degree of inaccessibility to active parts of the product
and degree of water)
Max. ambient RH (relative humidity) 85% at 20 °C
CE marking
ERP IV
Low voltage tests EN 60730-1* and EN 60730-2-9***
EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3
Uponor Smatrix Wave PULSE
|
Installation and operation manual
|
111

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor Smatrix Wave PULSE and is the answer not in the manual?

Uponor Smatrix Wave PULSE Specifications

General IconGeneral
TypeWireless Temperature Controller
Communication ProtocolRF (Radio Frequency)
CompatibilityUponor Smatrix Wave system
Operating Temperature Range0°C to 50°C
DisplayLCD
ControlWireless

Related product manuals