Use table stand instead
Attach the table stand to the thermostat using the wall bracket.
Register thermostat to room controller
1. Enter registration mode
Press and hold the OK button on the room controller until the LED for
channel 1 (or the first unregistered channel) flashes red.
2. Select a channel
Use buttons < or > to move the pointer (LED flashes red) to a
preferred channel.
3. Lock selected channel
Note
It is recommended to register all channels to the
thermostat at the same time.
Press the OK button to select the channel for registration. The LED
for the selected channel starts flashing green.
Select all channels to be registered to the thermostat and continue to
the next step.
4. Register thermostat
Gently press and hold the registration button on the thermostat,
release when the LED on the front of the thermostat starts flashing.
The selected channel LED in the room controller turns fixed green
and the registration is complete.
5. Exit registration mode
Press and hold the OK button on the room controller until the green
LEDs turn off to end registration and return to run mode.
To unregister already registered thermostats, see Unregister room
controller channels, Page 77.
6.4 Uponor Smatrix Wave T-166
Placement of thermostat
• Select an indoor wall and a position 1.3 m to 1.5 m above the
floor.
• Ensure that the thermostat is away from direct sunlight.
• Ensure that the thermostat will not be heated through the wall by
sunshine.
• Ensure that the thermostat is away from any source of heat, for
example television set, electronic equipment, fireplace,
spotlights, and so on.
• Ensure that the thermostat is away from any source of humidity
and water splashes (IP20).
• Ensure that the thermostat is positioned at least 40 cm away
from the room controller to avoid interference.