Table 35: Basic parameters G2.1
Index Parameter Min Max Unit Default Cust ID Description
P1.1.16 Sleep delay 0 3600 s 30 1017
The minimum
quantity of time
during which the
frequency has to
stay below the
sleep level before
the drive stops.
P1.1.17 Wake up level 0.00 100.00 % 25.00 1018
Gives the level for
the PID feedback
value wake-up
supervision. Uses
the set process
units.
P1.1.18 Wake up function 0 1 0 1019
0 = Wake-up at fall
below wake up
level (2.1.17)
1 = Wake-up at
exceeded wake up
level (2.1.17)
P1.1.19
Jogging speed
reference
0.00 P2.1.2 Hz 10.00 124
* = Parameter value can only be changed after the AC drive has been stopped.
PID CONTROL APPLICATION VACON · 103
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
5

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled

Related product manuals