Table 41: Protections, G2.7
Index Parameter Min Max Unit Default Cust ID Description
P2.7.25
Response to PT100
fault
0 3 0 740
0 = No response
1 = Warning
2 = Fault,stop acc.
to 2.4.7
3 = Fault,stop by
coasting
P2.7.26
PT100 warning
limit
-30.0 200.0 ºC 120.0 741
P2.7.27 PT100 fault limit -30.0 200.0 ºC 130.0 742