Table 55: Basic Settings (Control keypad: Menu M2 -> G2.2.1)
Index Parameter Min Max Unit Default Cust ID Description
P2.2.1.2
**
Motor potentiom-
eter ramp time
0.1 2000.0 Hz/s 10.0 331
The rate of change in
the motor potenti-
ometer reference
when it is increased
or decreased with
DI5 or DI6.
P2.2.1.3
**
Motor potentiom-
eter frequency
reference mem-
ory reset
0 2 1 367
0 = No reset
1 = Reset if stopped
or powered down
2 = Reset if powered
down
P.2.2.1.4
**
Adjust input 0 5 0 493
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = Fieldbus (see
group G2.9)
P2.2.1.5 Adjust minimum 0.0 100.0 % 0.0 494
P2.2.1.6 Adjust maximum 0.0 100.0 % 0.0 495
** = Parameter value can only be changed after the FC has been stopped.