EasyManuals Logo

Vacon NX series Applications Manual

Vacon NX series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
Table 2: Basic parameters G2.1
Index Parameter Min Max Unit Default Cust ID Description
P2.10 Motor cos phi 0.30 1.00 0.85 120
Find the value on
the rating plate of
the motor.
P2.11 Start function 0 2 0 505
0 = Ramp
1 = Flying start
2 = Conditional fly-
ing start
P2.12 Stop function 0 3 0 506
0 = Costing
1 = Ramp
2 = Ramp + Run
enable coast
3 = Coast + Run
enable ramp
P2.13 U/f optimisation 0 1 0 109
0 = Not used
1 = Automatic tor-
que boost
P2.14 I/O reference 0 3 0 117
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.15
Analogue input 2,
reference offset
0 1 1 302
0 = 0-20 mA
1 = 4 mA-20mA
P2.16
Analogue output
function
0 8 1 307
0 = Not used
1 = Output freq. (0-
f
max
)
2 = Freq. refer-
ence (0-f
max
)
3 = Motor speed
(0-Motor nominal
speed)
4 = Output current
(0-I
nMotor
)
5 = Motor torque
(0-T
nMotor
)
6 = Motor power
(0-P
nMotor
)
7 = Motor voltage
(0-U
nMotor
)
8 = DC-link volt
(0-1000V)
VACON · 16 BASIC APPLICATION
1
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled

Related product manuals