EasyManuals Logo

Vacon NX series Applications Manual

Vacon NX series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #191 background imageLoading...
Page #191 background image
Table 81: Torque control parameters, G2.10
Index Parameter Min Max Unit Default Cust ID Description
P2.10.8
Minimum fre-
quency for open
loop torque con-
trol
0.00 P2.1.2 Hz 3.00 636
The output fre-
quency limit below
which the drive
operates in the
frequency control
mode.
P2.10.9
Torque controller
P gain
0 32000 150 639
Gives the P gain
for the torque con-
troller in the open
loop control mode.
The P Gain value
1.0 causes a 1 Hz
change in the out-
put frequency
when the torque
error is 1% of the
motor nominal tor-
que.
P2.10.10
Torque controller
I gain
0 32000 10 640
Gives the I gain for
the torque control-
ler in the open loop
control mode. The
I Gain value 1.0
causes the inte-
gration to reach
1.0 Hz in 1 second
when the torque
error is 1% of the
motor nominal tor-
que.
NXP drives only
P2.10.11
Torque speed
limit (CL)
0 7 2 1278
0 = CL speed con-
trol
1 = Pos/neg freq
limits
2 = RampOut (-/+)
3 = NegFreqLimit-
RampOut
4 = RampOut-Pos-
FreqLimit
5 = RampOut Win-
dow
6 = 0-RampOut
7 = RampOut Win-
dow On/Off
P2.10.12
Torque reference
filtering time
0 32000 ms 0 1244
P2.10.13 Window negative 0.00 50.00 Hz 2.00 1305
MULTI-PURPOSE CONTROL APPLICATION VACON · 191
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
6

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C