Reduced time = set acc./deceler. time (parameters ID103, ID104; ID502, ID503) divided by the
factor R from Fig. 62.
Analogue input level zero corresponds to ramp times set by parameters. Maximum level
means a tenth of value set by parameter.
10
2
1
Signal range0
Factor R
Free
analogue
input
Fig. 62: Reducing of acceleration and deceleration times
402 SCALING OF TORQUE SUPERVISION LIMIT 6 (2.2.6.4)
See ID399.
The set torque supervision limit can be reduced with the free analogue input signal between
0 and the set supervision limit, ID349.
100%
Par. ID349
Signal range0
Torque
limit
Free
analogue
input
Fig. 63: Reducing torque supervision limit
403 START SIGNAL * 16 (2.2.7.1)
Signal selection 1 for the start/stop logic.
Default programming A.1.
404 START SIGNAL * 26 (2.2.7.2)
Signal selection 2 for the start/stop logic.
Default programming A.2.