Table 7: Output signals, G2.3
Index Parameter Min Max Unit Default Cust ID Description
P2.3.7
Digital output 1
function
0 16 1 312
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = FC overheat
warning
6 = Ext. fault or
warning
7 = Ref. fault or
warning
8 = Warning
9 = Reversed
10 = Preset speed
1
11 = At speed
12 = Mot. regulator
active
13 = OP freq. limit
1 superv.
14 = Control place:
IO
15 = Therminstor
fault/warning
16 = Fieldbus DIN1
P2.3.8
RO1 function 0 16 2 313 As parameter 2.3.7
P2.3.9 RO2 function 0 16 3 314 As parameter 2.3.7
P2.3.10
Output frequency
limit 1 supervision
0 2 0 315
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
P2.3.11
Output frequency
limit 1; Supervised
value
0.00 320.00 Hz 0.00 316
P2.3.12 *
Analogue output 2
signal selection
0.1 E.10 0.1 471
TTF programming
method used. See
8.9 "Terminal to
function" (TTF) pro-
gramming principle.
P2.3.13
Analogue output 2
function
0 8 4 472
As parameter 2.3.2
P2.3.14
Analogue output 2
filter time
0.00 10.00 s 1.00 473
0 = No filtering
VACON · 30 STANDARD APPLICATION