EasyManuals Logo

Vacon NX series Applications Manual

Vacon NX series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #312 background imageLoading...
Page #312 background image
Table 159: Selections for parameter ID607
Selection
number
Selection name Description
0 Controller switched off
1
Controller switched on (no
ramping)
Minor adjustments of OP frequency are made
2
Controller switched on (with
ramping)
Controller adjusts OP freq. up to max.freq.
When a value other than 0 is selected also the Closed Loop overvoltage controller becomes
active (in Multi-Purpose Control application).
608 UNDERVOLTAGE CONTROLLER 234567 (2.6.11)
See parameter ID607.
NOTE!
Over-/undervoltage trips may occur when controllers are switched out of operation.
Table 160: Selections for parameter ID608
Selection
number
Selection name Description
0 Controller switched off
1
Controller switched on (no
ramping)
Minor adjustments of OP frequency are made
2
Controller switched on (with
ramping)
Controller adjusts OP freq. up to max.freq.
When a value other than 0 is selected also the Closed Loop overvoltage controller becomes
active (in Multi-Purpose Control application).
609 TORQUE LIMIT 6 (2.10.1)
With this parameter you can set the torque limit control between 0.0 – 300.0 %.
In the Multi-Purpose Control application, the torque limit is selected between the minimum
of this parameter and the motoring and generating torque limits ID1287 and ID1288.
611 TORQUE LIMIT CONTROL I-GAIN 6 (2.10.3)
This parameter determines the I-gain of the torque limit controller. It is used in Open Loop
control mode only.
VACON · 312 PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled

Related product manuals