730 INPUT PHASE SUPERVISION 234567 (2.7.4)
Table 181: Selections for parameter ID730
Selection
number
Selection name Description
0 No response
1 Warning
2
Fault, stop mode after fault
according to ID506
3
Fault, stop mode after fault
always by coasting
The input phase supervision ensures that the input phases of the AC drive have an
approximately equal current.
731 AUTOMATIC RESTART 1 (2.20)
Use this parameter to enable the Automatic reset function.
Table 182: Selections for parameter ID731
Selection
number
Selection name Description
0 Disabled
1 Enabled
The function resets the following faults (max. three times) (see the product's User Manual:
Overcurrent (F1)
Overvoltage (F2)
Undervoltage (F9)
Frequency converter overtemperature (F14)
Motor overtemperature (F16)
Reference fault (F50)
PARAMETER DESCRIPTIONS VACON · 331