1252 SPEED STEP 6 (2.6.15.1, 2.6.25.25)
NCDrive parameter to help adjusting the speed controller. See closer NCDrive Tools: Step
response. With this tool you can give a step value to speed reference after ramp control.
1253 TORQUE STEP 6 (2.6.25.26)
NCDrive parameter to help adjusting the torque controller. See closer NCDrive Tools: Step
response. With this tool you can give step to torque reference.
1257 INCHING RAMP 6 (2.4.17)
Gives the acceleration and deceleration times when the Inching function is active.
The parameter is available for NXP drives only.
1276 EMERGENCY STOP MODE 6 (2.4.18)
Defines the action after the IO emergency input goes low. The parameter is available for NXP
drives only.
Table 202: Selections for parameter ID1276
Selection
number
Selection name Description
0 Coasting stop
1 Ramping stop
1278 TORQUE SPEED LIMIT, CLOSED LOOP 6 (2.10.6)
With this parameter the maximum frequency for the torque control can be selected.
VACON · 360 PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled

Related product manuals