EasyManua.ls Logo

Vacon NX series - Page 360

Vacon NX series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1252 SPEED STEP 6 (2.6.15.1, 2.6.25.25)
NCDrive parameter to help adjusting the speed controller. See closer NCDrive Tools: Step
response. With this tool you can give a step value to speed reference after ramp control.
1253 TORQUE STEP 6 (2.6.25.26)
NCDrive parameter to help adjusting the torque controller. See closer NCDrive Tools: Step
response. With this tool you can give step to torque reference.
1257 INCHING RAMP 6 (2.4.17)
Gives the acceleration and deceleration times when the Inching function is active.
The parameter is available for NXP drives only.
1276 EMERGENCY STOP MODE 6 (2.4.18)
Defines the action after the IO emergency input goes low. The parameter is available for NXP
drives only.
Table 202: Selections for parameter ID1276
Selection
number
Selection name Description
0 Coasting stop
1 Ramping stop
1278 TORQUE SPEED LIMIT, CLOSED LOOP 6 (2.10.6)
With this parameter the maximum frequency for the torque control can be selected.
VACON · 360 PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Related product manuals