NOTE!
This function is not available when flying start is selected for start function (ID505).
The parameter is available for NXP drives only.
1536 FOLLOWER FAULT 6 (2.11.8)
Defines the response in Master drive when a fault occurs in any of the follower drives. For
diagnostic purposes, when one of the drives trips to fault the master drive will send a
command to trigger Data Logger in all the drives.
Table 207: Selections for parameter ID1536
Selection
number
Selection name Description
0 No response
1 Warning
2
Fault, stop mode after fault
according to Stop function
1550 FLUX CIRCLE STABILATOR GAIN 6 (2.6.26.5)
Gain for flux circle stabilizer (0-32766)
1551 FLUX STABILATOR TC 6 (2.6.26.6)
Filter coefficient of id-current stabilizer.
1552 VOLTAGE STABILATOR TC 6 (2.6.26.11)
Damping rate of voltage stabilizer, (0-1000).
1553 VOLTAGE STABILATOR LIMIT 6 (2.6.26.11)
This parameter sets the limits for the voltage stabilizer output i.e. the max. and the min.
value for the correction term df in FreqScale.
1587 INV DELAYED DO1 6 (P2.3.1.5)
Inverts delayed digital output signal 1.
1588 INV DELAYED DO2 6 (P2.3.2.5)
Inverts delayed digital output signal 2.
1720 TORQUE STABILATOR LIMIT RATIO 6 (2.6.26.4)
Limit of torque stabilator output.
ID111 * ID1720 = Torque Stabilator Limit
VACON · 364 PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled