Fault
code
Fault
Subcode in
T.14
Possible cause How to correct the fault
36 Control unit NXS Control Unit can not
control NXP Power Unit and
vice versa
Change the control unit.
37 ** Device changed
(same type)
The option board was
replaced by a new one that
you have used before in the
same slot. The parameters
are available in the drive.
Reset the fault. The device is ready
for use. The drive starts to use the
old parameter settings.
38 ** Device added
(same type)
The option board was added.
You have used the same
option board before in the
same slot. The parameters
are available in the drive.
Reset the fault. The device is ready
for use. The drive starts to use the
old parameter settings.
39 ** Device removed An option board was
removed from the slot.
The device is not available. Reset
the fault.
40 Device unknown S1 =
Unknown
device
An unknown device was
connected (the power unit/
option board)
Ask instructions from the distribu-
tor near to you.
S2 =
Power1not
same type
as Power2
41 IGBT temperature IGBT Inverter Bridge over-
temperature protection has
detected too high a short
term overload current.
Do a check of the loading. Do a
check of the motor size. Make an
identification run.
42 Brake resistor
overtemperature
Brake resistor overtemper-
ature protection has detec-
ted too heavy braking.
Set the deceleration time longer.
Use external brake resistor.
VACON · 388 FAULT TRACING
9
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled