Table 15: Basic parameters G2.1
Index Parameter Min Max Unit Default Cust ID Description
P2.1.10 * Motor cos phi 0.30 1.00 0.85 120
Find the value on
the rating plate of
the motor.
P2.1.11 * I/O A reference 0 4 1 117
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
4 = Motor potenti-
ometer
P2.1.12 * I/O B reference 0 4 0 131
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
4 = Motor potenti-
ometer
P2.1.13 *
Keypad control
reference
0 3 2 121
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.14 *
Fieldbus control
reference
0 3 3 122
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.15 *
Jogging speed
reference
0.00 P2.1.2 Hz 0.00 124
* = Parameter value can only be changed after the AC drive has been stopped.