Table 15: Basic parameters G2.1
Index Parameter Min Max Unit Default Cust ID Description
P2.1.10 * Motor cos phi 0.30 1.00 0.85 120
Find the value on
the rating plate of
the motor.
P2.1.11 * I/O A reference 0 4 1 117
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
4 = Motor potenti-
ometer
P2.1.12 * I/O B reference 0 4 0 131
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
4 = Motor potenti-
ometer
P2.1.13 *
Keypad control
reference
0 3 2 121
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.14 *
Fieldbus control
reference
0 3 3 122
0 = AI1
1 = AI2
2 = Keypad
3 = Fieldbus
P2.1.15 *
Jogging speed
reference
0.00 P2.1.2 Hz 0.00 124
* = Parameter value can only be changed after the AC drive has been stopped.
VACON · 48 LOCAL/REMOTE CONTROL APPLICATION
3
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled