Table 16: Input signals, G2.2
Index Parameter Min Max Unit Default Cust ID Description
P2.2.7
AI1 signal inver-
sion
0 1 0 323
Analogue input 1 ref-
erence inversion
yes/no.
P2.2.8
AI1 signal filter
time
0.00 10.00 s 0.10 324
Analogue input 1 ref-
erence filter time,
constant.
P2.2.9
****
AI2 signal selec-
tion
0.1 E.10 A.2 388
TTF programming
method used. See
Chapter 8.9 "Termi-
nal to function" (TTF)
programming princi-
ple.
P2.2.10 AI2 signal range 0 2 1 325
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
P2.2.11
AI2 custom set-
ting minimum
-160.00 160.00 % 0.00 326
Analogue input 2
scale minimum.
P2.2.12
AI2 custom set-
ting maximum
-160.00 160.00 % 100.00 327
Analogue input 2
scale maximum.
P2.2.13
AI2 signal inver-
sion
0 1 0 328
Analogue input 2 ref-
erence inversion
yes/no.
P2.2.14
AI2 signal filter
time
0.00 10.00 s 0.10 329
Analogue input 2 ref-
erence filter time,
constant.
LOCAL/REMOTE CONTROL APPLICATION VACON · 51