EasyManua.ls Logo

Vacon NX series - Page 92

Vacon NX series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 31: Protections, G2.7
Index Parameter Min Max Unit Default Cust ID Description
P2.7.13 Stall protection 0 3 0 709
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.14 Stall current 0.00 2 x I
H
A 1
H
710
P2.7.15 Stall time limit 1.00 120.00 s 15.00 711
P2.7.16
Stall frequency
limit
1.00 P2.1.2 Hz 25.00 712
P2.7.17
Underload protec-
tion
0 3 0 713
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.18 UP fnom Torque 10.0 150.0 % 50.0 714
P2.7.19
UP Zero fre-
quency load
5.0 150.0 % 10.0 715
P2.7.20
Underload protec-
tion time limit
2.00 600.00 s 20.00 716
P2.7.21
Response to ther-
mistor fault
0 3 2 732
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
P2.7.22
Response to field-
bus fault
0 3 2 733
See P2.7.21
P2.7.23
Response to slot
fault
0 3 734
See P2.7.21
VACON · 92 MULTI-STEP SPEED CONTROL APPLICATION
4
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Related product manuals