Property Description/Value
Input impedances 200 Ω
Isolation Isolated from power supply
Overload protection 40 mA max. (reverse polarity protected)
Analog outputs
Number of analog outputs 4
Isolation Isolated from power supply
Selectable voltage output types 0 … 1 V, 0 … 5 V, 0 … 10 V, scalable
Selectable current output types 4 … 20 mA, 0 … 20 mA, scalable
Max. wire size
2.5 mm
2
(14 AWG)
Accuracy of analog outputs at +20 °C (+68 °F) ±0.05 % full scale
Temperature dependence ±0.005 % / °C full scale
External loads:
Current outputs R
L
< 500 Ω
0 … 1 V output R
L
> 2 kΩ
0 … 5 V and 0 … 10 V outputs R
L
> 10 kΩ
Relay outputs
Number and type of relays 2 pcs, SPDT
Max. switching power, current, voltage 30 W, 1 A, 40 V DC / 28 V AC
Max. wire size in PELV version
2.5 mm
2
(14 AWG)
Max. wire size in AC (mains) version
1.5 mm
2
(16 AWG)
Ethernet interface
Supported standards 10BASE-T, 100BASE-TX
Connector 8P8C (RJ45)
Supported protocols Modbus TCP/IP (port 502), HTTPS (port 8443)
1) The power supply option is selected when ordering the transmitter.
2) Transmitter shall be supplied by a Power Sourcing Equipment (PSE) unit which fulfils the
requirements of IEEE802.3at specifications.
Indigo510, Indigo520 User Guide M212287EN-N
108