Installation Manual _________________________________________________________________
56 __________________________________________________________________ M210485EN-B
Making a New Concrete Pad
NOTE
The transformation for the dimensions in this section:
10 mm 0.39 in.
12 mm 0.47 in.
40 mm 1.57 in.
50 mm 1.97 in.
70 mm 2.76 in.
150 mm 5.91 in.
300 mm 11.81 in.
400 mm 15.75 in.
600 mm 23.62 in.
1. Make a cast mould with steel reinforcements in accordance with
the design shown in Figure 40 below. Use the 12-mm deformed
steel. The distance between the horizontal layers should be
approximately 200 mm. Note that you can make the pads for the
guy wires similarly, but the reinforcement horizontal bar length
should be 300 mm instead of 400 mm as presented in Figure 40
below.
400 (300)
200
6
0
0
1
2
0306-030
Figure 40 Reinforcement for the Concrete Pads
The following numbers refer to Figure 40 above:
1 = 12 mm (0.47 in) deformed steel
2 = Cable conduit