Vertiv™ NetSure™ Control Unit (NCU) User Manual
140
Changing Programmable Parameters in the Settings Menu
To change a programmable parameter, select or enter a new value for the parameter then click on “Set” to change the value.
NOTE!
Settings that appear "grayed out" can only be made when the controller is in the "manual control" state. If the
controller is set for "automatic" control, change the “Auto/Manual State” setting first to the “Manual” setting.
NOTE!
Some parameters are not available for NCU configurations that enable NCU capability to receive status information
sent from FIAMM SoNick (Sodium Nickel) batteries.
Quick Settings Tab Programmable Parameter Descriptions
Site Settings: Enter a "Site Name", "Site Location", and "System Name".
Time Settings: Enter the time or select "Get Local Time from Connected PC".
In the Time Settings section, click on "Get Local Time from Connected PC" and then “Set” to automatically set the date and
time. To manually set the date and time, click on “the clock symbol” and enter the date and time. Then select the “Confirm”
button. See Figure 5.38. In the Time Settings section, click on “Set” to save the change.
Figure 5.38 Manual Date and Time Menu
Signal Settings:
- Float Charge Voltage: Float Charge output voltage setting.
- Equalize Charge Voltage: Equalize Charge output voltage setting.