Vertiv⢠NetSure⢠Control Unit (NCU) User Manual
Web
Interface Tab
Signal Manual Mode
Authority Level
Required - Web
Authority Level
Required - LCD
EIB-# Voltage Type (disable or type) -- Operator not available
EIB-# Block In-Use Num (0 to 8) -- Operator not available
Charging Efficiency (%) -- Engineer not available
Time to ##C10 Discharge (10 values in hr) -- Engineer not available
Clear Abnormal Bat Current (yes) -- Operator Operator
Settings / ECO ECO Mode (enable/disable) -- Operator Operator
Best Operating Point (%) -- Engineer Operator
Load Fluctuation Range (%) -- Engineer Operator
System Energy Saving Point (%) -- Engineer not available
Cycle Period (hr) -- Engineer Operator
All Rects On Time (min) -- Engineer Operator
Turn Off Delay (min) -- Engineer not available
Clear Cycle Alarm (yes) -- Engineer Operator
Settings / LVD LVD 1 & 2 (enable/disable) -- Operator Operator
LVD 1 & 2 Mode (voltage/time) -- Operator Operator
LVD 1 & 2 Disconnect Voltage (V) -- Operator Operator
LVD 1 & 2 Reconnect Voltage (V) -- Operator Operator
LVD 1 & 2 Reconnect Delay (min) -- Operator not available
LVD 1 & 2 Time (min) -- Operator Operator
LVD 1 & 2 Dependency (none/LVD1/LVD2/LVD3) -- Operator not available
LVD 1 & 2 High Temp Disconnect (enable/disable) -- Operator Operator
LVD Contactor Type (bi/mono/mono w-sample) -- Operator not available
LVD 1 & 2 Control (connected/disconnected) Yes Operator Operator
Settings / Temp Probes ## Temp# (none/ambient/battery) -- Operator not available
## Temp# High2 (deg) -- Engineer not available
## Temp# High1 (deg) -- Engineer not available
## Temp# Low (deg) -- Engineer not available
Settings / Rectifiers Current Limit (enable/disable) -- Operator Operator
Current Limit Point (A) -- Engineer Operator
HVSD (enable/disable) -- Operator not available
HVSD Limit (V) -- Engineer not available
Restart on HVSD (enable/disable) -- Engineer not available
HVSD Restart Time (sec) -- Engineer not available
Walk-in (enable/disable) -- Engineer Operator
Walk-in Time (sec) -- Engineer Operator
Sequence Start Interval (sec) -- Engineer Operator
Nominal AC Voltage (V) -- Operator Operator
Mains Failure Alarm Limit 1 (%) -- Operator Operator
Mains Failure Alarm Limit 2 (%) -- Operator Operator
Turn On When AC Over (yes or no) -- Engineer not available
Input Current Limit (A) -- Engineer not available
Mix HE Power (derated/non-derated) -- Engineer not available