Vertiv™ NetSure™ Control Unit (NCU) User Manual
177
Web
Interface Tab
Signal Manual Mode
Authority Level
Required - Web
Authority Level
Required - LCD
Diesel Generator Power Limit (enable/disable) -- Operator not available
Rectifier Trim (V) Yes Operator not available
DC On/Off Control (on all or off all) Yes Operator not available
AC On/Off Control on all or off all) Yes Operator not available
Rectifiers LED Control (stop or all flashing) Yes Operator not available
Fan Speed Control (auto or full) -- Operator not available
Confirm Rectifier ID/Feed (yes) -- Operator not available
Reset Rectifier IDs (yes) -- Operator not available
Clear Cycle Alarm (yes) -- Operator not available
Clear Rectifier Lost Alarm (yes) -- Operator Operator
Clear Rect Comm Fail Alarm (yes) -- Operator Operator
Settings / Battery Test Battery Test Control (stop/start) -- Operator Operator
AC Fail Test (enable/disable) -- Engineer not available
Constant Current Test (enable/disable) -- Engineer not available
Constant Current Test (A) -- Engineer not available
Short Test (enable/disable) -- Engineer not available
Short Test Cycle (days) -- Engineer not available
Short Test Time (min) -- Engineer not available
Short Test Max Difference (# X C10) -- Engineer not available
Test Voltage Level (V) -- Engineer Operator
End Test Voltage (V) -- Engineer Operator
End Test Time (min) -- Engineer Operator
End Test Capacity (%) -- Engineer Operator
Record Threshold (V) -- Engineer Operator
Number of Planned Tests (0 to 12) -- Engineer not available
Clear Bad Battery Alarm (yes) -- Operator Operator
Clear Battery Test Fail Alarm (yes) -- Operator Operator
Clear Discharge Curr Imbalance (yes) -- Operator Operator
Settings / Time Settings Specify Time (from PC or set manually) -- Engineer Operator
Local Zone (manual entry) -- Engineer not available
Get Time Automatically from Time Servers -- Engineer not available
Primary Server IP -- Engineer not available
Secondary Server IP -- Engineer not available
Interval to Adjust Time (min) -- Engineer not available
Advanced Settings /
Ethernet
IPV4 - IP Address -- Administrator Operator
IPV4 - Subnet Mask -- Administrator Operator
IPV4 - Default Gateway -- Administrator Operator
IPV4 - DHCP Server IP -- Administrator Operator
IPV6 - Link Local Address -- Administrator Operator
IPV6 - IPV6 Address -- Administrator Operator
IPV6 - Subnet Prefix -- Administrator Operator
IPV6 Default Gateway -- Administrator Operator