This procedure is used to restore all changes made to the NCU to factory defaults.
Procedure
ALERT! When this procedure is performed, the controller’s existing configuration and parameter settings will be lost. The
“SettingParam.tar” file is deleted. Before restoring the factory default configuration, if you have made changes to the NCU,
save the “SettingParam.tar” file (see “Backing Up the NCU Configuration” on page 48).
1. Click on the “Restore Defaults” button.
Figure 5.63 Restore Factory Defaults
2. Click “OK” to confirm to overwrite the existing "SettingParam.tar" file in memory with the stored "SettingParam.tar" file.
The controller will automatically reboot. All settings WILL BE restored to the defaults of the stored "SettingParam.tar" file.
NOTE!
After rebooting, you must exit your browser and re-login to see any changes made.
NOTE!
SOME SYSTEMS REQUIRE CHANGES TO THE NCU CONFIGURATION DURING FINAL TEST BEFORE BEING
SHIPPED. These systems are supplied with a USB memory device that contains a “SettingParam.tar” file as shipped. If
provided, the “SettingParam.tar” file has a seven-digit UIN (Unique Identification Number) preceding the “SettingParam.tar”
filename. The UIN identifies a “SettingParam.tar” file for use with a specific system. This file can be used to restore your
system to the configuration as shipped. Refer to “Reloading a Backed-Up NCU Configuration” on page 48 to reload the
supplied “SettingParam.tar” file.
TO RESTORE THESE SYSTEMS TO THE NCU CONFIGURATION AS SHIPPED, RESTORE DEFAULTS AS DESCRIBED ABOVE; THEN