EasyManuals Logo

Vertiv NetSure M830B User Manual

Vertiv NetSure M830B
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #202 background imageLoading...
Page #202 background image
Vertiv™ NetSure™ Control Unit (NCU) User Manual
192
Figure 5.68 Upload/Download File
ALERT! Never navigate from this Web page without first clicking on "Start Controller". If you do, you will not have Web
access. A manual system reset is required to restore Web access.
5. To download (from your computer into the controller) a configuration package, application ("All") package, language
package, or a "SettingParam.tar" file; click the "Browse..." button and navigate to the folder where the file to download is
located. Select the file to be downloaded and then click the "Download to Controller" button. Click "Start Controller" to restart
the controller with the downloaded file installed.
To upload a file to your computer, select "Configuration Package" or "Language Package" from the "File in Controller" drop-
down list box, and click on the "Upload to Computer" button to save the file to your computer. Select where you want the file
to be copied to on your computer. Click "Start Controller" to restart the Controller.
NOTE!
Ensure Internet Explorer security settings are set to enable a file to be copied to your computer.
NOTE!
A Configuration Package is a package of files containing all the default parameter settings and any User changes to
alarm severity levels, relay assignments, signal names and site information. Note that the Configuration Package is part of the
SettingParam.tarfile and does not typically need to be downloaded separately.
NOTE!
An Application “All” package file has both the application (software) and configuration package and is usually
supplied for an application upgrade.
NOTE!
A Language Package is a package of files containing all the default names of the parameters in two languages.
Typically these would be in English and Spanish. The language package cannot be changed by the User. Consult Vertiv if a
different language package is required.
NOTE!
A file named “SettingParam.tar is automatically created/appended by the Controller whenever a User (or the factory
at the time of shipment) makes changes to the NCU via the local display or Web Interface. This file also contains the
Configuration Package described above.

Table of Contents