Vertivâ„¢ NetSureâ„¢ Control Unit (NCU) User Manual
231
Table 6.1 Contents of the Controller’s MIB
Table 6.1
Identification Group
identManufacturer The name of the equipment manufacturer. R
identModel The manufacturers model designation of the power system. R
identControllerFirmwareVersion The firmware (software) version of the controller. R
identName The name of the power plant. This object should be set by the administrator. R/W
identSNMPCfgVer The SNMP configuration version. R
identControllerSerialNumber The serial number of this controller. R
System Group
systemStatus
Status of the complete plant (highest alarm). One of...
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled
R
systemVoltage System voltage, stored as mV, including positive or negative sign. R
systemCurrent System current, stored as mA, including positive or negative sign. R
systemUsedCapacity Used capacity, stored as percentage of the total capacity. R
Battery Group
psBatteryVoltage Battery voltage, stored as mV, including positive or negative sign. R
psTotalBatteryCurrent Battery current, stored as mA, including positive or negative sign. R
psLowestBatteryCapacity
Calculated capacity, stored as % of the total capacity.
Lowest available capacity for multiple battery strings.
R
Battery Table
psBatteryIndex Automatically generated index object. R
psBatteryCurrent Battery current in mA. R
psBatteryName Battery shunt name. R
psBatteryCapacity Battery capacity in Ah. R
psBatteryCapacityPercent Battery capacity in percent. R
psBatteryRatedCapacity Battery capacity in Ah*1000. R/W
Input Group
psInputLineAVoltage The AC line A voltage, stored as mV. R
psInputLineBVoltage The AC line B voltage, stored as mV. R
psInputLineCVoltage The AC line C voltage, stored as mV. R
psInputPhaseACurrent The AC Phase A current, stored as mA. R
psInputPhaseBCurrent The AC Phase B current, stored as mA. R
psInputPhaseCCurrent The AC Phase C current, stored as mA. R