Vertiv™ NetSure™ Control Unit (NCU) User Manual
232
Table 6.1
Temperature Group
psTemperature1 The first route temperature, stored as 0.001 Celsius degree. R
psTemperature2 The second route temperature, stored as 0.001 Celsius degree. R
Temperature Table
psTemperatureIndex Temperature probe number. R
psTemperatureMeasurement Temperature Value in degrees Centigrade * 1000. R
psTemperatureName Configured temperature probe name. R
psTemperatureType Temperature Probe Type. R
psTemperatureAlarmStatus Temperature Probe Alarm Status. R
psStatusCommunication The status of communication with the Power System. R
Battery Mode
psStatusBatteryMode
The status of battery modes.
FloatCharging (2),
ShortTest (3),
BoostChargingForTest (4),
MnualTesting (5),
PlanTesting (6),
ACFailTesting (7),
ACFail (8),
ManualBoostCharging (9),
AutoBoostCharging (10),
CyclicBoostCharging (11),
MasterBoostCharging (12),
MasterBateryTesting (13).
R
SM Series Group
psSMACNumber The number of SM AC module. R
psSMBATNumber The number of SM BAT module. R
psSMIONumber The number of SM IO module. R
Rectifier Group
psNumberOfInstalledRectifiers Number of rectifiers. R
psNumberOfRectifiersCommunicating Number of rectifiers communicating. R
psRectifiersUsedCapacity Used capacity, stored as % of the total capacity. R
Rectifier Table
psRectifierIndex Automatically generated index object. R
PsRectifierProductNumber Rectifier product number. R
PsRectifierHWVersion Rectifier hardware revision. R
psRectifierSWVersion Rectifier software revision. R
psRectifierSerialNumber Rectifier serial number. R
psRectifierCurrent Rectifier current. R
psRectifierIdent Rectifier physical location identifier. R
psRectifierFail
The type of alarm change. One of…
(1) Activated
(2) Deactivated
R