Vertivâ„¢ NetSureâ„¢ Control Unit (NCU) User Manual
233
Table 6.1
Distribution Load Table
psDistributionLoadCurrent Distribution current in mA. R
psDistributionLoadName Distribution name. R
Distribution General Table
psDistributionGeneralCurrent Distribution current in mA. R
psDistributionGeneralName Distribution name. R
Converter Group
numberOfInstalledConverters Number of converters. R
numberOfConvertersCommunicating Number of converters communicating. R
convertersUsedCapacity Used capacity, stored as % of the total capacity. R
psConverterVoltage Converter voltage in mV. R
psTotalConverterCurrent Total converter current in mA. R
Converter Table
psConverterIndex Automatically generated index object. R
psConverterProductNumber Converter product number. R
psConverterHWVersion Converter hardware revision. R
psConverterSWVersion Converter software revision. R
psConverterSerialNumber Converter serial number. R
psConverterCurrent Converter current. R
psConverterIdent Converter physical location identifier. R
psConverterFail
The type of alarm change.
(1) activated
(2) deactivated
R
Control Group
controlBatteryTest Control battery test, start (1), stop (0). R/W
controlRelay8 Control relay8, close (1), open (0). R/W
controlRelay7 Control relay7, close (1), open (0). R/W
controlRelay6 Control relay6, close (1), open (0). R/W
controlRelayTest Control relay test, auto (2), manual (1), disabled (0). R/W
Equipment Signal Table
psEquipmentSignalTableEntryIndex The unique sequence number of this equipment signal. R
psEquipmentSignalValue Indexed equipment signal value. R
Setting Group
settingFloatVoltage Float voltage setting in mV. R/W
settingEQChargeVoltage Equalize charge voltage stored as mV. R/W
settingBatteryCurrentLimit Battery charge current limit stored as thousandths of C10. R/W
settingResetBatteryCapacity Reset Battery Capacity. R/W
settingAutoEqualize
Automatic Equalize,
disabled (0),
enabled (1)
R/W
settingEQStartCurrent Equalize start current stored as thousandths of C10. R/W