EasyManua.ls Logo

Vertiv NetSure M830B - Page 243

Vertiv NetSure M830B
274 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv™ NetSure™ Control Unit (NCU) User Manual
233
Table 6.1
Distribution Load Table
psDistributionLoadCurrent Distribution current in mA. R
psDistributionLoadName Distribution name. R
Distribution General Table
psDistributionGeneralCurrent Distribution current in mA. R
psDistributionGeneralName Distribution name. R
Converter Group
numberOfInstalledConverters Number of converters. R
numberOfConvertersCommunicating Number of converters communicating. R
convertersUsedCapacity Used capacity, stored as % of the total capacity. R
psConverterVoltage Converter voltage in mV. R
psTotalConverterCurrent Total converter current in mA. R
Converter Table
psConverterIndex Automatically generated index object. R
psConverterProductNumber Converter product number. R
psConverterHWVersion Converter hardware revision. R
psConverterSWVersion Converter software revision. R
psConverterSerialNumber Converter serial number. R
psConverterCurrent Converter current. R
psConverterIdent Converter physical location identifier. R
psConverterFail
The type of alarm change.
(1) activated
(2) deactivated
R
Control Group
controlBatteryTest Control battery test, start (1), stop (0). R/W
controlRelay8 Control relay8, close (1), open (0). R/W
controlRelay7 Control relay7, close (1), open (0). R/W
controlRelay6 Control relay6, close (1), open (0). R/W
controlRelayTest Control relay test, auto (2), manual (1), disabled (0). R/W
Equipment Signal Table
psEquipmentSignalTableEntryIndex The unique sequence number of this equipment signal. R
psEquipmentSignalValue Indexed equipment signal value. R
Setting Group
settingFloatVoltage Float voltage setting in mV. R/W
settingEQChargeVoltage Equalize charge voltage stored as mV. R/W
settingBatteryCurrentLimit Battery charge current limit stored as thousandths of C10. R/W
settingResetBatteryCapacity Reset Battery Capacity. R/W
settingAutoEqualize
Automatic Equalize,
disabled (0),
enabled (1)
R/W
settingEQStartCurrent Equalize start current stored as thousandths of C10. R/W