Vertiv™ NetSure™ Control Unit (NCU) User Manual
234
Table 6.1
settingEQStartCapacity Auto Equalize start capacity in percent. R/W
settingEQStopCurrent Equalize stop current stored as thousandths of C10. R/W
settingEQStopDelay Equalize stop delay time stored as minutes. R/W
settingMaxEQChargeTime Maximum equalize charge time stored as minutes. R/W
settingSolarMode
Solar mode,
disabled (0),
rect-solar (1),
solar (2)
R/W
settingSolarFloatVoltage Solar float voltage stored as mV. R/W
settingSolarEQChargeVoltage Solar equalize voltage stored as mV. R/W
settingRectifierFloatVoltage Rectifier Float voltage stored as mV. R/W
settingRectifierEQChargeVoltage Rectifier Equalize voltage stored as mV. R/W
settingGeneratorFunction
Automatic Generator Control,
disabled (0),
voltage (1),
batterycapacity (2)
R/W
settingGeneratorStartVoltage Generator start voltage stored in mV. R/W
settingGeneratorManualStart
Generator Manual Start,
disabled (0),
active (1)
R/W
settingGeneratorStartCapacity Battery capacity in % * 1000. R/W
settingDIforGenerator
Digital input for Generator,
None (0),
DI2 (1),
DI3 (2),
DI4 (3),
DI5 (4),
DI6 (5),
DI7 (6)
R/W
settingUtilityPowerPresent
Utility Power is present,
No (0),
Yes (1)
R/W
settingBatteryCurrentLimitEnable
Battery Current Limit Enable,
Disabled (0)
Active (1)
R/W
settingRectifierCurrentLimitEnable
Rectifier Current Limit Enable
Disabled (0)
Active (1)
R/W
settingRectifierCurrentLimit Rectifier current limit stored as mA. R/W
settingCalculateBatteryCurrent
Calculate Battery Current
No (0)
Yes (1)
R/W