Vertiv™ NetSure™ Control Unit (NCU) User Manual
alarmCeaseTrap
An alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this
trap:
* alarmTime
Date and time when event occurred (local time), including timezone if supported by controller.
* alarmSeverity
Integer describing the severity of the alarm.
* alarmDescription
Free-text description of alarm.
* alarmType
Integer indicating type of alarm.
--
In Table 6.1, R means OID is read-only (GET), and R/W means OID can be read and modified (GET/SET).