EasyManuals Logo

YASKAWA G7 Series User Manual

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
4-18
Open-loop
vector
control
(A1-02 = 2)
Speed feedback
detection control
(AFR) gain
(N2-01)
Increasing torque
and speed response
Controlling hunting
and vibration in mid-
dle-range speeds (10
to 40 Hz)
1.00 0.50 to 2.00
Reduce the setting if
torque or speed response is
slow.
Increase the setting if
hunting or vibration
occurs.
Torque
compensation
primary delay time
constant (C4-02)
Increasing torque
and speed response
Controlling hunting
and vibration
20ms
20 to
100ms
Reduce the setting if
torque or speed response is
slow.
Increase the setting if
hunting or vibration
occurs.
Slip compensation
primary delay time
(C3-02)
Increasing speed
response
Improving speed
stability
200ms
100 to
500ms
Reduce the setting if speed
response is slow.
Increase the setting if the
speed is not stable.
Slip compensation
gain (C3-01)
Improving speed
accuracy
1.0 0.5 to 1.5
Increase the setting if
speed response is slow.
Reduce the setting if the
speed is too fast.
Open-loop
vector
control 1
(A1-02 = 2)
Carrier frequency
selection (C6-02)
Reducing motor
magnetic noise
Controlling hunting
and vibration at low
speeds (10Hz or
less)
Depends
on
capacity
0 to
default
Increase the setting if
motor magnetic noise is
high.
Reduce the setting if
hunting or vibration occurs
at low speeds.
Middle output
frequency voltage
(E1-08)
Minimum output
frequency voltage
(E1-10)
Improving torque at
low speeds
Controlling shock at
startup
Depends
on
capacity
and
voltage
Default to
Default + 1 or
2 V
*
Increase the setting if
torque or speed response is
slow.
Reduce the setting if shock
at startup is large.
Table 4.4 Adjusted User Parameters (Continued)
Control
Method
Name
(Parameter Number)
Performance
Factory
Setting
Recommended
Setting
Adjustment Method
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C