6-38
 Stabilizing Speed (Speed Feedback Detection Function)
The speed feedback detection control (AFR) function measures the stability of the speed when a load is sud-
denly applied, by calculating the amount of fluctuation of the torque current feedback value, and compensat-
ing the output frequency with the amount of fluctuation.
Related Parameters
Parameter
Number
Name
Description
Setting 
Range
Factory 
Setting
Change 
during 
Operation
Control Methods
Display
V/f 
V/f 
with 
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
n2-01
Speed 
Feedback 
Detection 
Control (AFR) 
Gain
Sets the internal speed feedback 
detection control gain in the 
automatic frequency regulator 
(AFR).
Normally, there is no need to 
change this setting. Adjust this 
parameter as follows:
- If hunting occurs, increase the 
set value.
- If response is low, decrease 
the set value.
Adjust the setting by 0.05 units 
at a time, while checking the 
response.
0.00 
to 
10.00
1.00 No No No A No No
AFR Gain
n2-02
Speed 
Feedback 
Detection 
Control (AFR) 
Time Constant
Sets the time constant to control 
the rate of change in the speed 
feedback detection control.
0
 to 
2000
50ms No No No A No No
AFR Time