User Parameter Tables
5-61
Protection Function Parameters: L
The following settings are made with the protection function parameters (L parameters): Motor selection
function, power loss ridethrough function, stall prevention function, frequency detection, torque limits, and
hardware protection.
Motor Overload: L1
User parameters for motor overloads are shown in the following table.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
L1-01
Motor
Overload
Protection
Selection
Sets the motor thermal
overload protection (OL1)
based on the cooling capacity
of the motor.
0: Disabled
1: Standard Fan Cooled
(< 10:1 motor)
2: Standard Blower Cooled
(≥10:1 motor)
3: Vector Motor
(1000:1 motor)
0 to 3 1 No Q Q Q Q Q 480H
MOL Fault
Select
L1-02
Motor
Overload
Protection
Time
Sets the motor thermal
overload protection (OL1)
time. A larger L1-02 time will
increase the time before an
OL1 fault will occur.
0.1
to
5.0
1.0 min No A A A A A 481H
MOL Time
Const
L1-03
Motor
Overheat
Alarm
Operation
Selection
Sets operation selection when
the motor temperature analog
input (H3-09 = E) exceeds the
OH3 alarm level (1.17V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3 3 No A A A A A 482H
Mtr OH
Alarm Sel
L1-04
Motor
Overheat
Fault
Operation
Selection
Sets stopping method when
the motor temperature analog
input
(H3-09 = E) exceeds the OH4
fault level (2.34V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
0 to 2 1 No A A A A A 483H
Mtr OH
Fault Sel
L1-05
Motor
Temperatur
e Input
Filter Time
This parameter adjusts the filter
on the motor temperature
analog input (H3-09 = E).
Increase to add stability,
decrease to improve response.
0.00
to
10.00
0.20sec No A A A A A 484H
Mtr Temp
Filter
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C