User Parameter Tables
5-61
 Protection Function Parameters: L
The following settings are made with the protection function parameters (L parameters): Motor selection 
function, power loss ridethrough function, stall prevention function, frequency detection, torque limits, and
hardware protection.
Motor Overload: L1
User parameters for motor overloads are shown in the following table.
Parameter 
Number
Name
Description
Setting 
Range
Factory 
Setting
Change 
during 
Operation
Control Methods
MODBUS
Register
Display
V/f 
V/f 
with 
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
L1-01
Motor 
Overload 
Protection 
Selection
Sets the motor thermal 
overload protection (OL1) 
based on the cooling capacity 
of the motor.
0: Disabled
1: Standard Fan Cooled 
    (< 10:1 motor)
2: Standard Blower Cooled
    (≥10:1 motor)
3: Vector Motor 
    (≤1000:1 motor)
0 to 3 1 No Q Q Q Q Q 480H
MOL Fault 
Select
L1-02
Motor 
Overload 
Protection 
Time
Sets the motor thermal 
overload protection (OL1) 
time. A larger L1-02 time will 
increase the time before an 
OL1 fault will occur.
0.1
to
5.0
1.0 min No A A A A A 481H
MOL Time 
Const
L1-03
Motor 
Overheat 
Alarm 
Operation 
Selection
Sets operation selection when 
the motor temperature analog 
input (H3-09 = E) exceeds the 
OH3 alarm level (1.17V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop 
3: Alarm Only
0 to 3 3 No A A A A A 482H
Mtr OH 
Alarm Sel
L1-04
Motor 
Overheat 
Fault 
Operation 
Selection
Sets stopping method when 
the motor temperature analog 
input 
(H3-09 = E) exceeds the OH4 
fault level (2.34V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
0 to 2 1 No A A A A A 483H
Mtr OH 
Fault Sel
L1-05
Motor 
Temperatur
e Input 
Filter Time
This parameter adjusts the filter 
on the motor temperature 
analog input (H3-09 = E). 
Increase to add stability, 
decrease to improve response.
0.00
to
10.00
0.20sec No A A A A A 484H
Mtr Temp 
Filter