Acceleration and Deceleration Characteristics
6-15
Acceleration and Deceleration Characteristics
This section explains the acceleration and deceleration characteristics of the Drive.
Setting Acceleration and Deceleration Times
Acceleration time indicates the time taken for the output frequency to climb from 0% to 100%. Deceleration
time indicates the time taken for the output frequency to reduce to 0%. The factory setting of the acceleration
time is C1-01, and the factory setting of the deceleration time is C1-02.
Related Parameters
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
C1-01
Acceleration
Time 1
Sets the time to accelerate from
zero to maximum frequency.
0.0 to
6000.0
*
10.0sec
YesQQ QQQ
Accel Time 1
C1-02
Deceleration
Time 1
Sets the time to decelerate from
maximum frequency to zero.
YesQQ QQQ
Decel Time 1
C1-03
Acceleration
Time 2
Sets the time to accelerate from
zero to maximum frequency when
selected via a multi-function
input.
YesAA AAA
Accel Time 2
C1-04
Deceleration
Time 2
Sets the time to decelerate from
maximum frequency to zero when
selected via a multi-function
input.
YesAA AAA
Decel Time 2
C1-05
Acceleration
Time 3
Sets the time to accelerate from
zero to maximum frequency when
selected via a multi-function
input.
No AA AAA
Accel Time 3
C1-06
Deceleration
Time 3
Sets the time to decelerate from
maximum frequency to zero when
selected via a multi-function
input.
No AA AAA
Decel Time 3
C1-07
Acceleration
Time 4
Sets the time to accelerate from
zero to maximum frequency when
selected via a multi-function
input.
No AA AAA
Accel Time 4
C1-08
Deceleration
Time 4
Sets the time to decelerate from
maximum frequency to zero when
selected via a multi-function
input.
No AA AAA
Decel Time 4
C1-10
Accel/Decel
Time Setting
Units
Sets the setting resolution of
C1-01 to C1-09
0: 0.01sec (0.00 to 600.00sec)
1: 0.1sec (0.0 to 6000.0sec)
0 or 1 1 No AA AAA
Acc/Dec Units
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals