6-16
* The setting range for accel/decel time will differ depending on C1-10 (Accel/Decel Time Units). If C1-10 is set to "0", then the setting range will change
to 0.00sec to 600.00sec.
* 1. Varies by Duty Rating
Setting Acceleration and Deceleration Time Units
Set the acceleration/deceleration time units using C1-10. Parameter C1-10 is set to 1 at the factory.
C1-11
Accel/Decel
Switch
Frequency
Sets the frequency for automatic
switching of accel / decel times.
Fout < C1-11:
Accel/Decel Time 4
Fout C1-11: Accel/Decel Time 1
Multi-function inputs
"Multi-Acc/Dec 1" and
"Multi-Acc/Dec 2" have priority
over C1-11.
Note: with Multi-Function Input,
Accel/Decel Time 1 and 2 will
take precedence.
0.0
to
400.0
*1
0.0Hz No AA AAA
Acc/Dec SW
Freq
C2-01
S-Curve
Characteristic
at Accel Start
S-curve is used to further soften
the starting and
stopping ramp. The longer the S-
curve time, the softer the starting
and stopping ramp.
Note: With this setting, accel/
decel times will be exactly half of
the start and finish times of the S-
curve characteristic time.
0.00
to
2.50
0.20sec No A A A A A
SCrv Acc @
Start
C2-02
S-Curve
Characteristic
at Accel End
0.00
to
2.50
0.20sec No A A A A A
SCrv Acc @
End
C2-03
S-Curve
Characteristic
at Decel Start
0.00
to
2.50
0.20sec No A A A A A
SCrv Dec @
Start
C2-04
S-Curve
Characteristic
at Decel End
0.00
to
2.50
0.00sec No A A A A A
SCrv Dec @
End
Set value Details
0 The acceleration/deceleration time settings range is 0.00 to 600.00 in units of 0.01 s.
1 The acceleration/deceleration time settings range is 0.00 to 600.00 in units of 0.1 s.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
Run command
Output frequency
Time
ON
OFF
C2-02 C2-03
C2-04
C2-01
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C