EasyManuals Logo

YASKAWA G7 Series User Manual

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #329 background imageLoading...
Page #329 background image
Individual Functions
6-111
Setting the V/f Pattern
In V/f control method, you can set the Drive input voltage and the V/f pattern as the need arises.
Related Parameters
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
E1-01
Input volt-
age setting
Set the Drive input voltage in 1 volt.
This setting is used as a reference value
in protection functions.
155.0 to
255.0
(240V)
310.0 to
510.0
(480V)*1
230.0V
or
460.0V
*1
No Q Q Q Q Q
Input Voltage
E1-03
V/f pattern
selection
0 to E: Select from the 15 preset
patterns.
F: Custom user-set patterns (Applicable
for settings E1-04 to E1-10.)
0 to F F No Q Q No No No
V/F Selec-
tion
E1-04
Max. output
frequency
To set V/f characteristics in a straight
line, set the same values for E1-07 and
E1-09. In this case, the setting for E1-08
will be disregarded.
Always ensure that the four frequencies
are set in the following manner:
E1-04 (FMAX) E1-06 (FA) > E1-07
(FB) E1-09 (FMIN)
40.0 to
400.0
*5
60.0Hz
*2
No Q Q Q Q Q
Max
Frequency
E1-05
Max. voltage
0.0 to
255.0
*1
230.0V
or
460.0V*
1*2
No Q Q Q Q Q
Max Voltage
E1-06
Base
frequency
0.0 to
400.0
*5
60.0Hz
*2
No Q Q Q Q Q
Base
Frequency
E1-07
Mid. output
frequency
0.0 to
400.0
3.0Hz
*2
No A A A No No
Mid
Frequency A
E1-08
Mid. output
frequency
voltage
0.0 to
255.0
*1
12.6Vac
or
25.3
*1 *2
No A A A No No
Mid Voltage
A
E1-09
Min. output
frequency
0.0 to
400.0
*5
0.5Hz
*2
No Q Q Q A Q
Min
Frequency
E1-10
Min. output
frequency
voltage
0.0 to
255.0
*1
2.3Vac
or
4.6Vac
*1 *2
No A A A No No
Min Voltage
Output voltage (V)
Frequency (Hz)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals