5-28
Reference Parameters: d
The following settings are made with the reference parameters (d parameters): Frequency references.
Preset Reference: d1
User parameters for frequency references are shown in the following table.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
d1-01
Frequency
Reference 1
Setting units are affected by
o1-03.
0
to
400.00
*
0.00Hz Yes Q Q Q Q Q 280H
Reference 1
d1-02
Frequency
Reference 2
Frequency reference when
multi-function input
"Multi-step speed reference 1"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 281H
Reference 2
d1-03
Frequency
Reference 3
Frequency reference when
multi-function input
"Multi-step speed reference 2"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 282H
Reference 3
d1-04
Frequency
Reference 4
Frequency reference when
multi-function input
"Multi-step speed reference 1, 2"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 283H
Reference 4
d1-05
Frequency
Reference 5
Frequency reference when
multi-function input
"Multi-step speed reference 3"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 284H
Reference 5
d1-06
Frequency
Reference 6
Frequency reference when
multi-function input
"Multi-step speed reference 1, 3"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 285H
Reference 6
d1-07
Frequency
Reference 7
Frequency reference when
multi-function input
"Multi-step speed reference 2, 3"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 286H
Reference 7
d1-08
Frequency
Reference 8
Frequency reference when
multi-function input
"Multi-step speed reference 1, 2, 3"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 287H
Reference 8
d1-09
Frequency
Reference 9
Frequency reference when
multi-function input
"Multi-step speed reference 4"
is ON. Setting units are
affected by o1-03.
0.00Hz Yes A A A A A 288H
Reference 9
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals