EasyManuals Logo

YASKAWA G7 Series User Manual

YASKAWA G7 Series
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #192 background imageLoading...
Page #192 background image
5-80
Digital Operator Parameters: o
The following settings are made with the Digital Operator parameters (o parameters): Multi-function
selections and the copy function.Monitor Select: o1
User parameters for Digital Operator Displays are shown in the following table.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
o1-01
User Monitor
Selection
Selects which monitor will be
displayed in the operation
menu upon power-up when
o1-02 = 4.
4 to 48 6 Yes A A A A A 500H
User Monitor
Sel
o1-02
User Monitor
Selection
After
Power-Up
Selects which monitor will
be displayed upon power-up.
1: Frequency Reference
(U1-01)
2: Output Frequency
(U1-02)
3: Output Current (U1-03)
4: User Monitor
(set by o1-01)
1 to 4 1 Yes A A A A A 501H
Power-On
Monitor
o1-03
Digital
Operator
Display
Selection
Sets the units of the
Frequency References (d1-01
to d1-17), the Frequency
Reference Monitors
(U1-01, U1-02, U1-05), and
the Modbus communication
frequency reference.
0: Hz
1: % (100% = E1-04)
2 RPM (Enter the
to number of motor
39: poles).
40 User display.
to Set the number
39999:desired at maximum
output frequency. 4
digit number. Number
of digits from the right
of the decimal point.
Example 1: o1-03 = 12000,
will result in frequency
reference from 0.0 to 200.0
(200.0 = Fmax).
Example 2: o1-03 = 21234,
will result in frequency
reference from 0.00 to 12.34
(12.34 = Fmax).
0
to
39999
0 No A A A A A 502H
Display
Scaling
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20
Storage Temperature-20°C to 65°C

Related product manuals