1-2
Varispeed G7 Introduction
Varispeed G7 Models
The Varispeed-G7 Series of Drives included two Drives in two voltage classes: 200-240V and 380-480V. Maximum motor
capacities vary from 20P4 to 2110 and 40P4 to 4300 (42 models).
Table 1.1 Varispeed
G7 Models
Voltage
Class
Maximum
Motor
Capacity
kW
Varispeed G7
Specifications
(Always specify through the protective structure when ordering.)
Output
Capacity
kVA
Basic Model Number
Open Chassis
(IEC IP00)
CIMR-G7
Enclosed Wall-mounted
(IEC IP20, NEMA 1)
CIMR-G7
200-240V
class
0.4 1.2 CIMR-G7U20P4
Remove the top and bottom
covers from the Enclosed
Wall-mounted model.
20P41
0.75 2.3 CIMR-G7U20P7 20P71
1.5 3.0 CIMR-G7U21P5 21P51
2.2 4.6 CIMR-G7U22P2 22P21
3.7 6.9 CIMR-G7U23P7 23P71
5.5 10 CIMR-G7U25P5 25P51
7.5 13 CIMR-G7U27P5 27P51
11 19 CIMR-G7U2011 2011
15 25 CIMR-G7U2015 20151
18.5 30 CIMR-G7U2018 20181
22 37 CIMR-G7U2022 - 20220
30 50 CIMR-G7U2030 20300 -
37 61 CIMR-G7U2037 20370 -
45 70 CIMR-G7U2045 20450 -
55 85 CIMR-G7U2055 20550 -
75 110 CIMR-G7U2075 20750 -
90 140 CIMR-G7U2090 20900 -
110 160 CIMR-G7U2110 21100 -
380-480V
class
0.4 1.4 CIMR-G7U40P4
Remove the top and bottom
covers from the Enclosed
Wall-mount model.
40P41
0.75 2.6 CIMR-G7U40P7 40P71
1.5 3.7 CIMR-G7U41P5 41P51
2.2 4.7 CIMR-G7U42P2 42P21
3.7 6.9 CIMR-G7U43P7 43P71
4.0 8.4 CIMR-G7U44P0 44P01
5.5 11 CIMR-G7U45P5 45P51
7.5 16 CIMR-G7U47P5 47P51
11 21 CIMR-G7U4011 40111
15 26 CIMR-G7U4015 40151
18.5 32 CIMR-G7U4018 40181
22 40 CIMR-G7U4022 - 40221
30 50 CIMR-G7U4030 - 40301
37 61 CIMR-G7U4037 - 40371
45 74 CIMR-G7U4045 - 40451
55 98 CIMR-G7U4055 40550 -
75 130 CIMR-G7U4075 40750 -
90 150 CIMR-G7U4090 40900 -
110 180 CIMR-G7U4110 41100 -
132 210 CIMR-G7U4132 41320 -
160 230 CIMR-G7U4160 41600 -
185 280 CIMR-G7U4185 41850 -
220 340 CIMR-G7U4220 42200 -
300 460 CIMR-G7U4300 43000 -
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 Series and is the answer not in the manual?

YASKAWA G7 Series Specifications

General IconGeneral
SeriesG7
Frequency50/60 Hz
Output VoltageMatches Input Voltage
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus, DeviceNet, Profibus, Ethernet
SafetySafe Torque Off (STO)
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Cooling MethodFan Cooled
Enclosure RatingIP20