5-54
Multi-function Contact Output Functions
Setting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
0 During run (ON: run command is ON or voltage is being output) Yes Yes Yes Yes Yes
1 Zero-speed Yes Yes Yes Yes Yes
2 Frequency agree 1 (L4-02 used.) Yes Yes Yes Yes Yes
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and
during frequency agree)
Yes Ye s Yes Yes Yes
4
Frequency (FOUT) detection 1 (ON: +L4-01 ≥ output frequency ≥ -L4-01, L4-02
used)
Yes Ye s Yes Yes Yes
5
Frequency (FOUT) detection 2 (ON: Output frequency ≥ +L4-01 or output
frequency ≤ -L4-01, L4-02 used)
Yes Ye s Yes Yes Yes
6
Drive operation ready
READY: After initialization, no faults
Yes Ye s Yes Yes Yes
7 During DC bus undervoltage (UV) detection Yes Yes Yes Yes Yes
8 During baseblock (ON: during baseblock) Yes Yes Yes Yes Yes
9 Frequency reference selection (ON: Frequency reference from Operator) Yes Yes Yes Yes Yes
A Run command selection status (ON: Run command from Operator) Yes Yes Yes Yes Yes
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque
detection at ON)
Yes Ye s Yes Yes Yes
C Loss of frequency reference (Effective when 1 is set for L4-05) Yes Yes Yes Yes Yes
D Braking resistor fault (ON: Resistor overheat or braking transistor fault) Yes Yes Yes Yes Yes
E
Fault (ON: Digital Operator communications error or fault other than CPF00 and
CPF01 has occurred.)
Yes Ye s Yes Yes Yes
F Not used. (Set when the terminals are not used.) - - - - -
10 Minor fault (ON: Alarm displayed) Yes Yes Yes Yes Yes
11 Fault reset command active Yes Yes Yes Yes Yes
12 Timer function output Yes Yes Yes Yes Yes
13 Frequency agree 2 (L4-04 used) Yes Yes Yes Yes Yes
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and
during frequency agree)
Yes Ye s Yes Yes Yes
15 Frequency detection 3 (ON: Output frequency ≤ -L4-03, L4-04 used) Yes Yes Yes Yes Yes
16 Frequency detection 4 (ON: Output frequency ≥ -L4-03, L4-04 used) Yes Yes Yes Yes Yes
17 Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes
18 Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at ON) Yes Yes Yes Yes Yes
19 Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at OFF) Yes Yes Yes Yes Yes
1A During reverse run (ON: During reverse run) Yes Yes Yes Yes Yes
1B During baseblock 2 (OFF: During baseblock) Yes Yes Yes Yes Yes
1C Motor selection (Motor 2 selected) Yes Yes Yes Yes Yes
1D During regenerative operation (ON: During regenerative operation) No No No Yes Yes
1E Restart enabled (ON: Restart enabled) Yes Yes Yes Yes Yes
1F Restart enabled (ON: Restart enabled) Yes Yes Yes Yes Yes